Abstract
This paper proposes a simple and accurate average value model (AVM) of a high-power half-bridge MMC for electromagnetic-Transient (EMT) studies. Least number of generic EMT blocks is used. Functioning as voltage source converter (VSC), the accuracy of a simplified MMC model would eventually be determined by its accuracy in reproducing the cell charging/discharging dynamics of the detailed models under all operating conditions. The validity of the proposed MMC average value model is verified against a detailed 1GW 21-level model in PSCAD. System dynamics and modelling accuracy of the AVM are tested with various operating conditions, including MMC startup, normal operation with power reversal, DC fault conditions, and MMC cell charging/discharging dynamics from AC and DC sides, with blocked or unblocked MMC status.
| Original language | English |
|---|---|
| Title of host publication | 4th International Symposium on Environment Friendly Energies and Applications, EFEA 2016 |
| Publisher | Institute of Electrical and Electronics Engineers Inc. |
| ISBN (Electronic) | 9781509007486 |
| DOIs | |
| Publication status | Published - 18 Nov 2016 |
| Event | 4th International Symposium on Environment Friendly Energies and Applications, EFEA 2016 - Belgrade, Serbia Duration: 14 Sept 2016 → 16 Sept 2016 |
Conference
| Conference | 4th International Symposium on Environment Friendly Energies and Applications, EFEA 2016 |
|---|---|
| Country/Territory | Serbia |
| City | Belgrade |
| Period | 14/09/16 → 16/09/16 |
UN SDGs
This output contributes to the following UN Sustainable Development Goals (SDGs)
-
SDG 7 Affordable and Clean Energy
Keywords
- Average value model
- detailed model
- HVDC transmission
- modular multilevel converter
- power system simulation
Fingerprint